NCC 2022 · Volume Two

NCC 2022 Volume Two 10.8.3 - Calculator

Calculates roof ventilation requirements at high level and at eave (applicable to builds in climate zone 6, 7 & 8)

1

Roof Space Ventilation

Enter the roof dimensions below to calculate the required open areas for compliant installations in applicable zones.

Longest horizontal dimension of the roof.
Click to see 10.8.3 applicable climate zones Map of Australia highlighting Climate Zones 6, 7 and 8

Under NCC 2022 Condensation Management provisions, roof space ventilation is a mandatory requirement for buildings located in Climate Zones 6, 7 and 8 only. If your project falls within any other climate zone, roof space ventilation is not required under these regulations. To confirm your climate zone, check which climate zone you're in here.

See Calculation Table
Roof Pitch Eaves Open Area High Level Open Area
Under 10°25,000 mm²/m (two opposing ends only)Not required
10° – 15°25,000 mm²/m5,000 mm²/m
15° – 75°, Non-Cathedral Ceiling7,000 mm²/m5,000 mm²/m
15° – 75°, Cathedral Ceiling25,000 mm²/m (7,000 + 18,000)5,000 mm²/m