NCC 2022 · Volume Two

Alpine Ventilation: NCC Condensation Management Calculator

Check exhaust ventilation and roof space ventilation requirements under NCC 2022 Part 10.8, and get a recommended product list for your job.

1

Exhaust Systems

NCC 2022 — 10.8.2
Determines the minimum mechanical exhaust airflow rate required.
2

Roof Space Ventilation

NCC 2022 — 10.8.3 / Table 10.8.3
Roof space ventilation provisions apply to Climate Zones 6, 7 and 8 only.
Measured horizontally — the longest plan dimension of the roof.
Only relevant for pitches of 15° or more — cathedral ceilings require a higher eaves open area.
Roof Pitch Eaves Open Area High Level Open Area
Less than 10°25,000 mm²/m (two opposing ends only)Not required
10° to less than 15°25,000 mm²/m5,000 mm²/m
15° to less than 75° (Standard ceiling)7,000 mm²/m5,000 mm²/m
15° to less than 75° (Cathedral / Raked ceiling)25,000 mm²/m (7,000 + 18,000)5,000 mm²/m